In this post, we will see how to manage and view saved passwords in Google Chrome web browser. Chrome will save your login usernames and passwords for the various websites you visit. When you save them, it will automatically complete the sign-in fields for you the next time you visit the websites. Get all your solutions of Chrome only atWindowsFish

875 Via De La Paz, Ste D Pacific Palisades 90272 Call us at (310) 459-1605

Email Us

Featuring Single Compression Gland for Armored and Unarmored Cable (Type A gland)

 

 

PRODUCT DESCRIPTION

“A” type glands are certified Flameproof Ex d, Increased Safety Ex e, Restricted Breathing Ex nR and Dust Protected Ex ta. They are suitable for use in Zone 1 and 2 for Gas Groups IIA, IIB and IIC and additionally for use in Zones 20, 21 and 22 for Dust Groups IIIA, IIIB and IIIC. Commonly referred to as “stuffing glands”, they provide a controlled pull resistant environmental displacement seal on the cable outer sheath, minimizing damage to cables that exhibit “cold flow” characteristics. The gland maintains IP66 & IP68 to 50 metres. It is supplied with an IP O-ring seal as standard on metric entry threads. Options are available for use with LSOH cables and extreme temperature applications. The “A” version is designed to accommodate unarmored and armored cables where sealing and retention is required only on the outer sheath.  

COMPLIANCE STANDARDS:

EN 60079-0, EN 60079-1, EN 60079-7, EN 60079-15, EN 60079-31 IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 60079-31 & IEC 60529 C22.2 (see certificate), CAN/CSA 60079-0/1/7, UL514B, UL1203, UL2225, UL50E, ANSI/UL 60079-0/7, ISA 60079-31  

CERTIFICATION

ATEX II 1D 2G Ex d IIC Gb / Ex e IIC Gb / Ex ta IIIC Da II 3G Ex nR IIC Gc
IECEx Ex d IIC Gb / Ex e IIC Gb / Ex ta IIIC Da
CEC – Canada (except size 12) Class I Zone 1 Ex d IIC / Ex e II Class I Division 2, Groups A, B, C & D Class II Division 1, Groups E, F & G Class III, Enclosure Type 4X
NEC – USA Class I Zone 1 AEx e IIC Gb / Class II Zone 20 AEx ta IIIC Da Class II Division 1, Groups E, F & G Class III, Enclosure Type 4X
EAC Exd IICU / Exe IIU / ExnR IIU
INMETRO – Brazil Ex d IIC Gb / Ex e IIC Gb / Ex ta IIIC Da / Ex nR IIC Gc
SAC – China Ex d IIC / Ex e IIC
UKRAINE Ex d IIC X / Ex e II X
CCoE – India Petroleum Rules 2002 (PESO)
ABS Specified ABS Rules
LLOYD’S Enclosure Systems (Part 1B)
RMRS Part XI of RS Rules for the classification & construction of sea-going ships (ed. 2014)

 

CERTIFICATION NUMBER:

ATEX SIRA 01ATEX1272X & SIRA 09ATEX1221X
IECEx IECEx SIR 07.0096X
CEC – Canada CSA 1356011
NEC – USA CSA 2627370
EAC RU C-GB.ГБ06.В.00098
INMETRO – Brazil NCC 13.2012 X
SAC – China NEPSI GYJ16.1399X
UKRAINE UA.TR.047.C.0408-13 & 2937
CCoE – India PESO P365300/2 & P365300/5
ABS 14-LD463991-1-PDA
LLOYD’S 10/00056(E1)
RMRS 14.02755.315

 

EXAMPLE PART NUMBERING:

(2LBF/NP/20/M20)

A Type of gland featuring controlled displacement sealing
2 Neoprene Seals (2) – Silicone (3) – Neoprene/Lead (1) – Silicone/Lead (4)
L Peppers Standard Designation
B Aluminum (A) / Brass (B) / Stainless Steel (S)
F Multiple Certification

OPTIONS:

C PVC Shroud (C) – PCP Shroud (P) – Silicone LSOH Shroud (3)
K-V-H Locknut & Nylon (K), Fibre (V) or PTFE (H) IP Washer
T Including Earth Tag
S Including Serrated Washer
1 1 Quantity per kit
NP Nickel Plated

 

20 Gland shell size
M20 M20 x 1.5mm Male Entry Thread

 

OPTIONAL ACCESSORIES

LOCKNUT Brass (ACBLN) / St Steel (ACSLN) / Aluminum (ACALN)
EARTH TAG Brass (ACBET) / St Steel (ACSET) / Aluminum (ACAET)
IP WASHERS Nylon (ACNSW) / Fibre (ACFSW) / PTFE (ACPSW)
SERRATED WASHERS Stainless Steel (ACSSW)
SHROUDS PVC (ACSPVC) / PCP (ACSPCP) / Silicone LSOH (ACSSIO)

 

IP RATING: IP66 & IP68 (50 metres – 7 Days ), Type 4X
OPERATING TEMP: Neoprene Seals -35ºC to +90ºC / Silicone Seals -60ºC to +180ºC
MATERIALS: Aluminum, Brass or Stainless Steel
PLATING Electroless Nickel

 

CABLE GLAND SELECTION TABLE (ALL DIMENSIONS IN mm)

Notes:

• Gland size does not necessarily equate to the entry thread size. • The IP O-ring seal is only available on metric entry threads. IP washers can be supplied for tapered entry threads. • Dimensions (A) & (B) may differ for glands with non metric entry threads. Please refer to our “Thread Reference Tables” for specific dimensions. • Assembly instructions must be read prior to installation and adhered to in full. • Peppers supplies cable glands with parallel entry threads that conform to the flameproof threaded joint requirements of IEC/EN 60079-1 and other equivalent standards. They usually incorporate a thread run out according to the available machining techniques and will not have a full form thread for the entire length. Peppers Cable Glands Limited will not be held responsible for clients’ installations where this has not been taken into account. • When selecting IP Washer & Shroud material for use with glands, please be aware of the accessories temperature range to ensure they are suitable for the intended installation. • Where approval in addition to ATEX, IECEx and CSA is required, this must be clearly requested at time of inquiry / order.   PDF DOWLOAD

Sometimes you want to download a lot of videos from different websites. For example, YouTube or Vimeo. At the same time on a computer installed Microsoft Windovs. In this case, there is nothing easier than to download TubeMate for Windows

What if you don’t have a Mac but still want to use iMessage on your Windows PC? There is a way to get fulfill your wish. Download iPadian on your Windows. It’s an emulator a third party software (Just like) which creates a virtual iOS ecosystem on your Widows; letting you install Apple’s popular Messages on your Windows. Learn how to use iMessage for PC only at MacMetric